These cables are partially water blocked, fire resistant, flame retardant, low smoke and halogen free, used for emergency control, power and lighting systems that need to be operational during a 1100°C hydrocarbon fire.
IEC 60092-354 | IEC 60092-351 |
IEC 60092-359 | IEC 60332-1 |
IEC 60331-21 | IEC 60332-3-22 |
IEC 60754-1,2 | IEC 61034-1,2 |
NEK 606:2004 | VG 95218 part 29? |
?
l???? Conductors: Circular tinned annealed stranded copper to IEC 60228 class 2.
l???? Conductor Screen: Semi conducting material.
l???? Insulation: Halogen-free EPR. XLPE can be offered as an option.
l???? Insulation Screen: Semi conducting material and tinned copper wire braid.
l???? Filler: Water blocking fillers, if required.
l???? Bedding: Halogen free compound, PETP wrapping tape will be applied over the bedding, if required.
l???? Armour: Tinned copper wire braid, PETP wrapping tape will be applied over the braiding, if required.
l???? Water Blocking Elements: Water blocking tape and strings for providing longitudinal water tightness.
l???? Inner Sheath: Halogen free thermosetting compound, SHF2, coloured red.
l???? HC-fire protection: Extruded thermoplastic fire protection compound.
l???? Taping: Lapped glass fibre tape.
l??? Outer Sheath 1: Flame retardant halogen-free thermoplastic compound, SHF1, coloured red.
l??? Outer Sheath 2: Polyurethane for providing transversal water tightness, PE is optional,but can not meet low smoke standard.
Nominal Cross Section Area | mm2 | 70 | 95 | 120 | 150 | 185 | 240 | 300 |
Nominal Conductor Diameter | mm | 10.3 | 12.2 | 13.8 | 15.1 | 17.0 | 19.6 | 21.9 |
Maximum DC Resistant@20˚C | O/km | 0.27 | 0.195 | 0.154 | 0.126 | 0.1 | 0.0762 | 0.0607 |
Continuous Current Rating@45˚C1 Core | A | 242 | 293 | 339 | 389 | 444 | 522 | 601 |
Continuous Current Rating@45˚C3 Core | A | 169 | 205 | 237 | 272 | 311 | 365 | 421 |
Short Circuit Current 1s | A | 10020 | 13590 | 17170 | 21460 | 26470 | 34340 | 42930 |
Operating Voltage | KV | 6/10 | 6/10 | 6/10 | 6/10 | 6/10 | 6/10 | 6/10 |
Ambient Temperature Correction Factors | 35 | 40 | 45 | 50 | 55 | 60 | 65 | 70 | 75 | 80 |
Rating Factor | 1.1 | 1.05 | 1.0 | 0.94 | 0.88 | 0.82 | 0.74 | 0.67 | 0.58 | 0.47 |
Construction No. of cores×Cross section (mm2) |
|||||
Nominal Insulation Thickness mm |
Nominal Diameter Over Bedding mm |
Nominal Diameter Over Inner Sheath mm |
Nominal Overall Diameter mm |
Nominal Weight kg/km |
|
1×70 | 3.4 | 23.5 | 30 | 64.4±2 | 5481 |
1×95 | 3.4 | 25.5 | 32 | 67.3±2 | 6195 |
1×120 | 3.4 | 27.5 | 34 | 69.3±2 | 6657 |
1×150 | 3.4 | 28.5 | 35 | 70.3±2 | 7004 |
1×185 | 3.4 | 30.5 | 36.5 | 71.8±2 | 7686 |
1×240 | 3.4 | 33 | 39 | 75.2±2 | 8663 |
1×300 | 3.4 | 35 | 41.5 | 77.7±2 | 9744 |
3×50 | 3.4 | 47 | 55 | 91.4±2 | 11519 |
3×95 | 3.4 | 54 | 62.5 | 99.8±2 | 14942 |
3×150 | 3.4 | 60 | 70.5 | 108.8±2 | 18270 |